| Place of Origin |
Zhejiang China (Mainland) |
| Brand Name |
TIANAN |
| Model Number |
HSSPT-120000/33 |
| Usage |
Rectifier |
| Phase |
Three |
| Coil Structure |
Other |
| Coil Number |
Other |
Technical parameters of products: Type :HSSPT-120000/33 Connecting symbol : Dyd0 Rated capacity : 120000 kVAPhase : 3 Rated voltage : 33/1.143 kV Frequency : 50 Hz Rated current : 2099.5/74083 A Method of cool : OFWF Temperature rise limit : 50/55 K Insulation level : LI200AC85/LI8AC5 Other : Oil code of 25Location of switch1111421VVoltage ratio V33000/549.333000/84633000/935.233000/1143KVACapacity70478108575120000120000kW*Load loss kW600640716579KwNo-load loss7076.578.583%Impedance voltage24.112.412.08.2%No-load current///0.302Stray losses are not included: about 54kW The site transformer Max. load losses is 980kW